| Voltage supply |
230V AC ± 10%, 45...63 Hz, 30VA |
| Device fuse |
1,0 A M (medium time-lag) |
| Measurement method |
Vertical illuminanance |
| Max. measurement range |
0....100.000 lx |
| Min. measurement range |
0........1.000 lx |
| |
Please report desired measurement range with your order.
Other measurement ranges by request.
The measurement range is a factory setting and cannot be changed on-site! |
| Output signal |
4,0...20,0 mA |
| |
Bürde < 500 Ω |
| Output fuse |
32 mA M (medium time-lag) |
| Interference protection |
Varistor for power supply
Micro fuse and suppressing diode for output |
| Connector terminal |
Screw terminal for cable cross sections 0,5...2,5 mm² |
| |
|
| Optical properties |
|
| Visual field |
Max 160° coverage angle |
| |
|
| Physical properties |
|
| Housing |
Stainless steel (mat. No.: 1.4571)
Requirement class I according to German ZTV-Ing. Teil 5, Abschnitt 4 |
| Diffusor |
Glas, schmutzabweisend |
| Cable bushing |
1 x M16 cable glare for outer cable diameter 4,5…10 mm
1 x M12 cable glare for outer cable diameter 3,0…..7 mm
Cable entry from the rear, take into account the required clearance. |
| Dimensions |
Housing complete with protective cover H x W × L = 120 x 110 × 260 mm
(Potential arrestor protrudes additionally 30mm, see picture)
Tube without attachments Ø × L = 70 × 170 mm |
| Protection class |
IP65 |
| Weight |
1,8 kg |
| Temperature range |
Ambient temperature: -30°...+70°C
Storage temperature: -30°...+70°C |
| Mounting position |
Horizontal, shadowing is to be excluded
Clearance above sensor > 250mm
Clearance behind sensor > 250 mm |